Continuity testing
What is the purpose of continuity testing?
The purpose of this task is to test for a break in the circuit.
There are two methods of performing this task. Either by a continuity tester ( a 3 volt battery and test bulb or L.E.D.) or by performing the milli-volt drop test using a volt meter. The latter is the preferred method but you must know both and always use the method as defined in the maintenance manual.
Before testing any circuit, The following should be performed:
SO ALWAYS FOLLOW THE MAINTENANCE MANUAL.
If performing the milli-volt drop test, you may now apply power as required to put that circuit into its usual working condition but
Continuity tester method
To perform a continuity test using this method you must simply connect the positive side of the battery to one end of the circuit, connect the bulb or L.E.D. to the negative side of the battery and then connect the end of the circuit, that is not connected to anything, to the bulb. If there is an unbroken circuit, the bulb will light up and vise versa. This must always be performed on a circuit isolated from other power sources.
Millivolt drop test
This test is more preferred because not only will it tell you if you have a circuit, but it will also signify the condition of the circuit. This test is accomplished by referring to the maintenance manuals for the allowable voltage drop and test connection points. Once you have consulted with the maintenance manual and put the aircraft circuit breakers, fuses and switches in the desired configuration, Then connect your voltmeter to the test connection points and take your volt reading. Now compare your results with the allowable limits in the aircraft manual.
Please remember the following:-
Insulation testing
Insulation testing is performed to check that the insulation of the wires within a circuit has not degraded or failed. This task is performed by following the directions in the maintenance manual of which normally follow the steps laid out below:-
The tests now differ for the two types of systems in use, The Double pole and the single pole, The latter being the system commonly in use today, but because there are still old aircraft flying and you must know everything, as well as have a maintenance manual, both methods are shown below:
Single pole system
Place one lead connector on to the earth ( normaly the casing or aircraft structure and then the other lead connector to the wires or leads of the circuit to be tested. If the resistance is less than allowed in reference to the aircraft manual, then the exact wire which has failed must be traced and the fault located and rectified.
Please note that although this method allows a bunch of wires to be tested together to save time, It is preferred that each wire be tested individually.
Double pole system
To test the insulation on a double pole system, you should follow the following process and order. First measure the resistance between the positive and negative battery leads ( leads must be disconnected from the battery),then the resistance between earth and the positive battery lead, and then do the same for the negative battery lead.
Post Testing
After the insulation tests have been performed, then it is necessary that the wiring is connected back up to its ancillary equipment and that the circuit breakers are reset to the required positions. Once the system has been restored, then a function test must be performed in accordance with the maintenance manual before release to service.